Skip to product information
1 of 1

Zenith Sales & Calibrations Pty Ltd

RM-5000 Multi Gas Monitor System

RM-5000 Multi Gas Monitor System

Regular price $0.00 AUD
Regular price Sale price $0.00 AUD
Sale Sold out
Shipping calculated at checkout.

RM-5000 Multi Gas Monitor System

  • Bar meter and digital multi-indication
  • High level of visibility
  • Low power consumption
  • Support RS-485 communication function
  • Global standard
  • Combatible with RM-570A/580 series
View full details

A multi-channel gas monitor system for monitoring combustible gases, oxygen, and toxic gases.

It can be used with existing multi/single cas of RM-570A / RM-580 series by use of connection case 5000-CC without new installation work. Also it is compatible as a replacement to use in existing facility expansion. RM 5000

Related Services


Fixed Systems Turnkey Solutions

  • Design, Consultations, and Engineering
  • Installation
  • Start-up
  • Training
  • System Maintenance
RM-5000 Series
GP-5001 NC-5001 NC-5001W NP-5001 SP-5001 GH-5001
Detection Gas
Combustible Combustible Inert Gases Combustible/Toxic
Indication
Character LCD (Digital and bar meter) Green, Yellow, Red (3-colors)
Type of acceptable detector head
Catalytic combustion new ceramic Thermal conductivity Special catalytic/semiconductor combination sensor semiconductor
Acceptable input signal
Direct sensor signal
Applicable cable
CVV-4C CVVS-4C CVV-4C CVVS-3C
Max distance
Max 2.0km
Output signal
Ouput of electric power transmission (non-isolated) 4-20mADC, max loop load 300Ω
Alamr indication
Flashing or lighting lamp: Red (alarm1), Red (alarm2), Self-latching or Auto reset, Lock-in
Trouble Alarm
Orange lamp flashing (fault), non-latching / content indication
Alarm relays
Normally energized or de-energized normally-open or closed contact rated 0.5A at 100VAC, 1.5A at 30VDC (resistive)
Operating condition
-10~+40C (14 F to 104 F), 10~90% RH (non-condensing)
Power supply
24VDC
Power consumption
Max 7W
Dimensions & weight
Approx. 1.16w x 4.72h x 3.62d inches
Structure
Card type with front display enclosed in a case (a single-unit or multi-unit case)
  • LPG, LNG utlities
  • Refineries
  • Chemical plants
  • Semi-conductor manufacturing plants
  • Engineering, public works
  • Power station
  • Iron and steel works
  • Automotive plating processes

Download Product Datasheet  : Download